Air Balance Calculator

Compare design CFM against measured CFM per branch.

Reviewed by James Whitfield · How we check our maths

Your values

ⓘ Live results

Results
Percent of design
78.7%
Difference
-32 CFM
Action
Open damper or check restriction
Target band
135–165 CFM

Quick answer

A branch is considered balanced when measured airflow sits within 10% of its design value.

The formula

% of design = measured / design x 100

Worked example

Worked example

Using the values the calculator loads with.

Inputs

  • Design airflow150 CFM
  • Measured airflow118 CFM

Result

  • Percent of design78.7%
  • Difference-32 CFM
  • ActionOpen damper or check restriction
  • Target band135–165 CFM

How to use the Air Balance Calculator

  1. 1Record the design airflow for the branch from the duct drawing.
  2. 2Measure the delivered airflow with a flow hood or traverse.
  3. 3Adjust the balancing damper and re-measure.

Frequently asked questions

What tolerance is acceptable?

Most specifications allow plus or minus 10% on each branch and 5% on the system total.

Should I balance with a dirty filter?

No — fit a clean filter first, otherwise every reading shifts once it is changed.