HVAC & Airflow

Cooling Tower Airflow Calculator

Airflow and evaporation for a cooling tower.

Enter your values

ⓘ Live results

Results
Heat rejected
3,000,000 BTU/h
In tons
250
Airflow
55,556 CFM
Evaporation
6 gpm
Makeup with 3 cycles
9 gpm

Quick answer

Cooling tower airflow is set by the heat rejected and the enthalpy rise of the air passing through the fill.

CFM ≈ heat rejected / (4.5 x enthalpy rise)

How to use the Cooling Tower Airflow Calculator

  1. 1Enter the condenser water flow and the range you need across the tower.
  2. 2Use 10-14 Btu/lb enthalpy rise for a typical induced draft tower.
  3. 3Add blowdown to evaporation to size makeup water.

Worked example

Using the values the calculator loads with:

Inputs

  • Water flow600 gpm
  • Range (in - out)10 °F
  • Air enthalpy rise12 Btu/lb

Results

  • Heat rejected3,000,000 BTU/h
  • In tons250
  • Airflow55,556 CFM
  • Evaporation6 gpm
  • Makeup with 3 cycles9 gpm

Frequently asked questions

What is approach?

The gap between leaving water temperature and ambient wet bulb — a 5°F approach tower is much larger than a 10°F one.

Cycles of concentration?

Higher cycles save water but need better chemical treatment to avoid scale.

About this calculator