HVAC & Airflow

Data Center CFM per kW Calculator

Rack airflow from IT load and delta T.

Enter your values

ⓘ Live results

Results
CFM per kW
158
Airflow per rack
1,264 CFM
Total room airflow
12,637 CFM
Total IT load
80 kW
Cooling required
22.7 tons

Quick answer

IT equipment needs roughly 126 CFM per kW at a 20°F rise, scaling inversely with the delta T you design for.

CFM = kW x 3412 / (1.08 x ΔT °F)

How to use the Data Center CFM per kW Calculator

  1. 1Enter the average IT load per rack in kW.
  2. 2Choose the delta T across the equipment — 20°F is common, 30°F for containment designs.
  3. 3Make sure the CRAC units can deliver the total airflow, not just the tonnage.

Worked example

Using the values the calculator loads with:

Inputs

  • IT load8 kW
  • Temperature rise20 °F
  • Number of racks10

Results

  • CFM per kW158
  • Airflow per rack1,264 CFM
  • Total room airflow12,637 CFM
  • Total IT load80 kW
  • Cooling required22.7 tons

Frequently asked questions

Why does delta T matter so much?

Raising delta T from 20 to 30°F cuts required airflow by a third, saving large amounts of fan energy.

Containment?

Hot or cold aisle containment prevents recirculation and lets you run higher supply temperatures.