HVAC & Airflow

Duct Leakage Percent Calculator

Duct leakage rate as a percent of system airflow.

Enter your values

ⓘ Live results

Results
Leakage percentage
3.8%
Rating
Excellent (meets tight code limits)
Leakage in CFM
45 CFM

Quick answer

Duct leakage is reported as a percentage of total fan airflow; most energy codes require total leakage under 4-6% for new construction.

Leakage % = leakage CFM / total system CFM x 100

How to use the Duct Leakage Percent Calculator

  1. 1Get the leakage CFM from a duct blaster test at 25 Pa (CFM25).
  2. 2Divide by the system's total design or measured airflow.
  3. 3Compare against your energy code's target, commonly 4% to total or 6 CFM per 100 sq ft to outside.

Worked example

Using the values the calculator loads with:

Inputs

  • Measured leakage45 CFM25
  • Total system CFM1200 CFM

Results

  • Leakage percentage3.8%
  • RatingExcellent (meets tight code limits)
  • Leakage in CFM45 CFM

Frequently asked questions

What is CFM25?

It's the airflow through duct leaks measured at a standardized 25 Pascal test pressure, used to normalize results between systems.

How is leakage reduced?

Mastic sealant on all joints, seams and boots, plus sealing the air handler cabinet itself.