HVAC & Airflow

Duct Size by Tonnage Calculator

Trunk and return duct size from AC tonnage.

Enter your values

ⓘ Live results

Results
System airflow
1,200 CFM
Trunk round diameter
16.6 in
Return duct diameter (600 FPM)
19.1 in
Registers at 120 CFM each
10

Quick answer

A common rule of thumb is 400 CFM per ton of cooling, which is then used to size the main trunk and return duct.

CFM = tons x 400, then size duct at design velocity

How to use the Duct Size by Tonnage Calculator

  1. 1Enter the equipment's rated tonnage.
  2. 2Use 400 CFM per ton as the standard residential design airflow.
  3. 3Size the trunk and return duct from that airflow at their respective design velocities.

Worked example

Using the values the calculator loads with:

Inputs

  • System size3 tons
  • Trunk velocity800 FPM

Results

  • System airflow1,200 CFM
  • Trunk round diameter16.6 in
  • Return duct diameter (600 FPM)19.1 in
  • Registers at 120 CFM each10

Frequently asked questions

Is 400 CFM per ton always right?

It's a solid rule of thumb; humid climates sometimes target 350 CFM per ton for better dehumidification.

Does this replace a full Manual D design?

No, it's a quick sizing check — a full room-by-room and friction-rate design is still the accurate method.