ERV/HRV Balance Calculator

Supply/exhaust airflow balance for a heat/energy recovery ventilator.

Enter your values

ⓘ Live results

Results
Imbalance
10%
Net pressure tendency
Slightly negative
Within 10% tolerance?
Yes
Average airflow
100 CFM

Quick answer

Balanced ventilation systems should have supply and exhaust CFM within about 10% of each other to avoid pressurizing the home.

Imbalance % = |supply - exhaust| / average x 100

How to use the ERV/HRV Balance Calculator

  1. 1Measure supply and exhaust airflow with a balometer or flow hood at each register.
  2. 2Total each side and compute the percentage imbalance.
  3. 3Adjust dampers or fan speeds until within about 10%.

Worked example

Using the values the calculator loads with:

Inputs

  • Measured supply airflow95 CFM
  • Measured exhaust airflow105 CFM

Results

  • Imbalance10%
  • Net pressure tendencySlightly negative
  • Within 10% tolerance?Yes
  • Average airflow100 CFM

Frequently asked questions

Is some imbalance ever intentional?

Yes — some codes call for a small negative bias to reduce moisture intrusion into wall cavities.

What causes drift over time?

Dirty filters or clogged cores slow one airstream more than the other, so recheck balance annually.