Evaporator Airflow Per Ton Calculator

CFM per ton for an evaporator coil.

Enter your values

ⓘ Live results

Results
CFM per ton
400
Assessment
Within typical comfort-cooling range
Sensible heat ratio implication
Balanced sensible/latent

Quick answer

Standard comfort-cooling evaporator coils are designed around 350-450 CFM per ton, with refrigeration coils often lower.

CFM per ton = airflow / tons

How to use the Evaporator Airflow Per Ton Calculator

  1. 1Measure or take the design airflow across the coil.
  2. 2Divide by the coil's rated tons of cooling.
  3. 3Compare against the 350-450 CFM/ton comfort cooling benchmark.

Worked example

Using the values the calculator loads with:

Inputs

  • Measured or design airflow1200 CFM
  • Cooling capacity3 tons

Results

  • CFM per ton400
  • AssessmentWithin typical comfort-cooling range
  • Sensible heat ratio implicationBalanced sensible/latent

Frequently asked questions

What about refrigeration coils?

Refrigeration and dehumidification-focused coils run lower, often 100-250 CFM per ton.

Why does low CFM/ton risk frosting?

Too little airflow lets coil surface temperature drop below freezing, icing the fins.