HVAC & Airflow

Furnace Airflow Calculator

CFM and temperature rise for a furnace.

Enter your values

ⓘ Live results

Results
Output capacity
64,000 BTU/h
Airflow
1,185 CFM
CFM per 10,000 BTU output
185
Rise check
Within typical 30-70°F range
Airflow at 45°F rise
1,317 CFM

Quick answer

Furnace airflow is output BTU divided by 1.08 times the temperature rise, which must fall inside the nameplate range.

CFM = output BTU / (1.08 x rise)

How to use the Furnace Airflow Calculator

  1. 1Read input rating and efficiency from the furnace nameplate.
  2. 2Measure supply and return temperatures to get the actual rise.
  3. 3Adjust blower speed until the rise sits mid-range on the nameplate.

Worked example

Using the values the calculator loads with:

Inputs

  • Input rating80000 BTU/h
  • Efficiency80 %
  • Measured temperature rise50 °F

Results

  • Output capacity64,000 BTU/h
  • Airflow1,185 CFM
  • CFM per 10,000 BTU output185
  • Rise checkWithin typical 30-70°F range
  • Airflow at 45°F rise1,317 CFM

Frequently asked questions

Rise too high?

Airflow is too low — check the filter, closed registers and duct restriction before touching the blower tap.

Rise too low?

Airflow is excessive, which can cause cold drafts and, on some furnaces, condensation in the heat exchanger.