HVAC & Airflow

Latent Heat Load Calculator

Moisture removal load from airflow and grain difference.

Enter your values

ⓘ Live results

Results
Latent load
20,400 BTU/h
In tons
1.7
Water removed
19.4 pints/hour
In kW
5.98

Quick answer

Latent load equals 0.68 times CFM times the grains of moisture removed per pound of air.

BTU/h = 0.68 x CFM x Δgrains

How to use the Latent Heat Load Calculator

  1. 1Measure grains of moisture entering and leaving the coil with a psychrometric app.
  2. 2Enter airflow and the grain difference.
  3. 3Compare against the equipment's rated latent capacity.

Worked example

Using the values the calculator loads with:

Inputs

  • Airflow1200 CFM
  • Grain difference25 gr/lb

Results

  • Latent load20,400 BTU/h
  • In tons1.7
  • Water removed19.4 pints/hour
  • In kW5.98

Frequently asked questions

Typical grain drop?

A well-performing residential coil removes 15-30 grains per pound.

Low latent removal?

Usually too much airflow across the coil or an oversized system that short cycles.

About this calculator

Results are estimates for general information. For medical, legal, structural or financial decisions, confirm with a qualified professional.