HVAC & Airflow

Office Ventilation CFM Calculator

Total and outdoor airflow for an office.

Enter your values

ⓘ Live results

Results
Total supply air
2,500 CFM
Outdoor air
240 CFM
Outdoor air fraction
9.6%
Per person total
138.9 CFM
Cooling capacity implied
6.3 tons

Quick answer

Offices typically need 1 CFM per square foot of supply air with 5 CFM per person plus 0.06 per sq ft of outdoor air.

OA = 5 x people + 0.06 x area

How to use the Office Ventilation CFM Calculator

  1. 1Enter the floor area and realistic design occupancy.
  2. 2Set the supply rate — 1 CFM per sq ft suits most offices.
  3. 3Confirm the outdoor air damper can actually deliver the OA figure.

Worked example

Using the values the calculator loads with:

Inputs

  • Floor area2500 sq ft
  • Occupants18
  • Supply rate1 CFM/sq ft

Results

  • Total supply air2,500 CFM
  • Outdoor air240 CFM
  • Outdoor air fraction9.6%
  • Per person total138.9 CFM
  • Cooling capacity implied6.3 tons

Frequently asked questions

Why is my office stuffy?

Usually the outdoor air damper is closed or the economiser has failed; check CO2 levels.

Dense meeting rooms?

Size those separately — they can need 3-4 times the area-based rate.