HVAC & Airflow

Parking Garage Ventilation Calculator

Code airflow for an enclosed parking garage.

Enter your values

ⓘ Live results

Results
Required exhaust
15,000 CFM
Air changes
5
Fans at 12,000 CFM each
2
CO-controlled low speed (50%)
7,500 CFM
Annual saving with CO control
Often 50-80% of fan energy

Quick answer

Enclosed parking garages are commonly ventilated at 0.75 CFM per square foot of floor area.

CFM = area x 0.75

How to use the Parking Garage Ventilation Calculator

  1. 1Enter the enclosed floor area and clear height.
  2. 2Apply your local rate — 0.75 CFM per sq ft is the common default.
  3. 3Add CO and NO2 sensors so fans modulate instead of running flat out.

Worked example

Using the values the calculator loads with:

Inputs

  • Garage floor area20000 sq ft
  • Ceiling height9 ft
  • Code rate0.75 CFM/sq ft

Results

  • Required exhaust15,000 CFM
  • Air changes5
  • Fans at 12,000 CFM each2
  • CO-controlled low speed (50%)7,500 CFM
  • Annual saving with CO controlOften 50-80% of fan energy

Frequently asked questions

Is CO control allowed?

Most modern codes permit demand control down to a minimum, with sensors and alarms.

Where do exhaust points go?

Split between high and low level, since CO mixes but heavier vapours settle.