HVAC & Airflow

Series Fans Pressure Calculator

Combined static pressure of identical fans in series.

Enter your values

ⓘ Live results

Results
Ideal combined pressure
3 in wc
Realistic combined pressure
2.7 in wc
Loss to interaction
0.3 in wc

Quick answer

Ideal series pressure is the sum of each fan's pressure at a given flow, but real systems typically achieve 85-95% of that sum due to inlet turbulence between stages.

SP_combined = n x SP_single x derate

How to use the Series Fans Pressure Calculator

  1. 1Enter the number of identical fans staged in series and each one's pressure at the shared flow rate.
  2. 2Apply an interaction derate for turbulence between stages (typically 85-95%).
  3. 3Use the realistic combined pressure to check the system can be overcome.

Worked example

Using the values the calculator loads with:

Inputs

  • Number of fans in series2
  • Pressure per fan alone1.5 in wc
  • Interaction derate90 %

Results

  • Ideal combined pressure3 in wc
  • Realistic combined pressure2.7 in wc
  • Loss to interaction0.3 in wc

Frequently asked questions

Why stage fans in series instead of one bigger fan?

Series staging (like inline duct boosters) can be a simpler retrofit than replacing a single fan with a larger unit.

Does spacing between fans matter?

Yes — more distance between stages reduces turbulent interaction and improves the combined pressure.

About this calculator