Smoking Room Ventilation Calculator

Exhaust airflow for a designated smoking room.

Enter your values

ⓘ Live results

Results
Design exhaust
563 CFM
Per-occupant basis
480 CFM
15 ACH basis
563 CFM
Supply air (90%)
506 CFM
Net negative
56 CFM

Quick answer

Smoking rooms are typically exhausted at 60 CFM per occupant and held negative to surrounding spaces.

CFM = 60 x occupants, minimum 15 ACH

How to use the Smoking Room Ventilation Calculator

  1. 1Enter the room's occupancy and dimensions.
  2. 2Use whichever basis gives the higher airflow.
  3. 3Supply about 90% of the exhaust so the room stays negative and smoke cannot migrate.

Worked example

Using the values the calculator loads with:

Inputs

  • Occupants8
  • Floor area250 sq ft
  • Ceiling height9 ft

Results

  • Design exhaust563 CFM
  • Per-occupant basis480 CFM
  • 15 ACH basis563 CFM
  • Supply air (90%)506 CFM
  • Net negative56 CFM

Frequently asked questions

Can air cleaners replace exhaust?

No — filtration removes particles but not the gases, so exhaust is still required.

Door treatment?

Self-closing doors and a vestibule dramatically reduce leakage.