HVAC & Airflow

Toilet Room Exhaust Calculator

Exhaust CFM for a standalone toilet or powder room.

Enter your values

ⓘ Live results

Results
Required exhaust
50 CFM
Fixture basis
50 CFM
Area basis
35 CFM
Duct at 700 FPM
3.6 in dia

Quick answer

Small toilet rooms are commonly exhausted at 50 CFM per water closet intermittent, or 20 CFM continuous, whichever the local code and IMC table require.

CFM = max(50 per WC intermittent, 20 per WC continuous, area x 1)

How to use the Toilet Room Exhaust Calculator

  1. 1Enter the room area and number of water closets.
  2. 2Choose intermittent or continuous fan operation.
  3. 3Take the larger of the fixture-based and area-based airflow.

Worked example

Using the values the calculator loads with:

Inputs

  • Room area35 sq ft
  • Water closets1
  • Fan operationIntermittent (occupancy sensor)

Results

  • Required exhaust50 CFM
  • Fixture basis50 CFM
  • Area basis35 CFM
  • Duct at 700 FPM3.6 in dia

Frequently asked questions

Do I need makeup air for a small toilet room?

Usually the undercut door provides enough transfer air; no dedicated makeup air unit is needed at this scale.

Continuous vs intermittent?

Continuous low-CFM operation controls odour better in commercial restrooms with steady traffic.

About this calculator

Results are estimates for general information. For medical, legal, structural or financial decisions, confirm with a qualified professional.