HVAC & Airflow

Trash Room Exhaust Calculator

Exhaust airflow for a refuse or trash compactor room.

Enter your values

ⓘ Live results

Results
Required exhaust
250 CFM
Area basis
225 CFM
10 ACH basis
250 CFM
Pressure
Hold room negative to corridor to contain odour

Quick answer

Trash and refuse rooms are commonly exhausted continuously at about 1-2 CFM per square foot, or a minimum of 10 air changes per hour, held negative to adjacent spaces.

CFM = max(area x rate, volume x 10 ACH / 60)

How to use the Trash Room Exhaust Calculator

  1. 1Enter the trash room's floor area and ceiling height.
  2. 2Compare the area-based rate to a minimum 10 air-changes-per-hour target.
  3. 3Hold the room negative to adjoining corridors so odours do not migrate.

Worked example

Using the values the calculator loads with:

Inputs

  • Room area150 sq ft
  • Ceiling height10 ft
  • Area-based rate1.5 CFM/sq ft

Results

  • Required exhaust250 CFM
  • Area basis225 CFM
  • 10 ACH basis250 CFM
  • PressureHold room negative to corridor to contain odour

Frequently asked questions

Does refrigeration replace the need for exhaust?

No — refrigerated trash rooms still need exhaust ventilation for odour and moisture control, especially near the compactor.

Should the fan run continuously?

Yes, continuous low-level exhaust is standard for trash rooms to prevent odour buildup between pickups.