Fan Static Pressure Calculator
System resistance a fan must overcome.
Enter your values
ⓘ Live results
Results
- Total static pressure
- 0.68 in w.c.
- In pascals
- 169
- Largest component
- duct
- Select fan at
- design CFM against 0.68 in w.c.
Quick answer
A fan must be selected at the system's total static pressure, not in free air, or delivered airflow falls short.
TSP = duct loss + filter + coil + grilles
How to use the Fan Static Pressure Calculator
- 1Enter each component's pressure drop at design airflow.
- 2Use a dirty-filter value, not a clean one, so the system still works months later.
- 3Select the fan from its curve at the total static shown.
Worked example
Using the values the calculator loads with:
Inputs
- Duct loss0.25 in w.c.
- Filter loss0.15 in w.c.
- Coil loss0.2 in w.c.
- Grilles and registers0.08 in w.c.
Results
- Total static pressure0.68 in w.c.
- In pascals169
- Largest componentduct
- Select fan atdesign CFM against 0.68 in w.c.
Frequently asked questions
Why does free-air CFM mislead?
Fan ratings in free air ignore the system; a 400 CFM fan may deliver 250 CFM once ducted.
What is a typical residential total?
Around 0.5 in w.c. is the design target for a standard air handler.