HVAC & Airflow

Grease Duct Velocity Calculator

Check grease duct velocity against code minimums.

Enter your values

ⓘ Live results

Results
Duct velocity
1,350 FPM
Duct area
1.78 sq ft
Code minimum
1500 FPM (verify local minimum, some require 1800-2000)
Status
Below minimum — reduce duct size or add airflow

Quick answer

Grease ducts must maintain at least 1500 FPM (some jurisdictions require 1800-2000 FPM) to keep grease entrained and moving rather than settling in the duct.

Velocity = CFM / duct cross-sectional area

How to use the Grease Duct Velocity Calculator

  1. 1Enter the actual duct airflow (from balancing report or design).
  2. 2Enter the duct's internal width and height.
  3. 3Confirm velocity meets or exceeds your jurisdiction's minimum, typically 1500 FPM.

Worked example

Using the values the calculator loads with:

Inputs

  • Duct airflow2400 CFM
  • Duct width16 in
  • Duct height16 in

Results

  • Duct velocity1,350 FPM
  • Duct area1.78 sq ft
  • Code minimum1500 FPM (verify local minimum, some require 1800-2000)
  • StatusBelow minimum — reduce duct size or add airflow

Frequently asked questions

What happens below minimum velocity?

Grease settles inside the duct instead of being carried to the filters/exhaust fan, creating a serious fire hazard.

Can duct be oversized instead?

No — oversized grease duct is a common code violation because it drops velocity below the self-cleaning threshold.