HVAC & Airflow

Hood Static Pressure Calculator

Total static for a hood exhaust system.

Enter your values

ⓘ Live results

Results
Total static pressure
1 in wc
Duct portion
0.15 in wc
Filter portion
0.6 in wc
Select fan at
1.15 in wc
In Pa
249

Quick answer

Hood system static pressure is the sum of filter loss, duct friction and discharge loss.

TSP = filter + duct + fitting + discharge losses

How to use the Hood Static Pressure Calculator

  1. 1Get the filter loss from the hood submittal at design airflow.
  2. 2Add duct friction from length plus fitting equivalent length.
  3. 3Select the fan at 10-15% above the calculated total.

Worked example

Using the values the calculator loads with:

Inputs

  • Filter loss0.6 in wc
  • Duct length40 ft
  • Friction rate0.15 in wc/100 ft
  • Fitting equivalent length60 ft
  • Discharge loss0.25 in wc

Results

  • Total static pressure1 in wc
  • Duct portion0.15 in wc
  • Filter portion0.6 in wc
  • Select fan at1.15 in wc
  • In Pa249

Frequently asked questions

Why add a margin?

Grease build-up raises resistance over time; the margin keeps capture velocity as the system loads.

Typical total?

Most commercial hood systems land between 1.0 and 1.75 in wc.

About this calculator