Grow Room Exhaust Fan Calculator

Extraction for a sealed or vented grow room.

Enter your values

ⓘ Live results

Results
Fan size
790 CFM
Heat removal requirement
632 CFM
Air exchange requirement
320 CFM
Heat load
4,094 BTU/h
Air changes achieved
148 ACH

Quick answer

Extraction must remove both stale air and light heat; the heat load usually sets the fan size in a sealed room.

CFM = watts x 3.412 / (1.08 x allowed °F rise)

How to use the Grow Room Exhaust Fan Calculator

  1. 1Add up the wattage of lights, pumps and ballasts in the room.
  2. 2Set the temperature rise you can live with over intake air — 5–8 °F is realistic.
  3. 3Size the fan on whichever requirement is larger, then add 25% for filters.

Worked example

Using the values the calculator loads with:

Inputs

  • Total heat load1200 W
  • Allowed temperature rise6 °F
  • Room volume320 cu ft

Results

  • Fan size790 CFM
  • Heat removal requirement632 CFM
  • Air exchange requirement320 CFM
  • Heat load4,094 BTU/h
  • Air changes achieved148 ACH

Frequently asked questions

Why is my room still hot?

Either the fan is undersized for the heat load or intake air is already warm — you cannot exhaust below ambient.

Do LEDs change this?

LEDs make less heat per usable photon, but every watt drawn still becomes heat in the room.