Heat Load CFM Calculator
Ventilation needed to remove a watt or BTU heat load.
Enter your values
ⓘ Live results
Results
- Airflow required
- 632 CFM
- Heat load
- 10,236 BTU/h
- In kW
- 3
- Equivalent tons
- 0.85
- In m³/h
- 1,074
Working
- 110,236 / (1.08 x 15) = 632 CFM
Quick answer
Airflow to remove heat equals the load in BTU/h divided by 1.08 times the allowable temperature rise.
CFM = BTU/h / (1.08 x ΔT)
How to use the Heat Load CFM Calculator
- 1Choose watts or BTU/h and enter the total heat load.
- 2Set the temperature rise you can tolerate between intake and exhaust.
- 3Size fans for that airflow with headroom for filters and grilles.
Worked example
Using the values the calculator loads with:
Inputs
- Load unitWatts
- Heat load3000 W or BTU/h
- Allowed temperature rise15 °F
Results
- Airflow required632 CFM
- Heat load10,236 BTU/h
- In kW3
- Equivalent tons0.85
- In m³/h1,074
- 10,236 / (1.08 x 15) = 632 CFM
Frequently asked questions
Why does a smaller ΔT need more air?
The air can only carry so much heat per degree, so a tighter temperature target demands proportionally more airflow.
Is ventilation enough for a server room?
Only if outdoor air is reliably cooler than your target; otherwise you need mechanical cooling.