HVAC & Airflow

Heat Pump Airflow Calculator

Airflow checks for a heat pump in both modes.

Enter your values

ⓘ Live results

Results
Design airflow
1,200 CFM
Heating airflow
1,260 CFM
Aux heat rise
26.3 °F
Supply temp with aux at 70°F return
96 °F
Aux capacity
34,120 BTU/h

Quick answer

Heat pumps generally need 400 CFM per ton in cooling and slightly more in heating to keep supply temperatures comfortable.

CFM = tons x 400; strip rise = kW x 3412 / (1.08 x CFM)

How to use the Heat Pump Airflow Calculator

  1. 1Enter the system tonnage and target CFM per ton.
  2. 2Add the auxiliary strip heat capacity in kW.
  3. 3Verify the temperature rise with strips on is inside the air handler's listed range.

Worked example

Using the values the calculator loads with:

Inputs

  • System size3 tons
  • CFM per ton400 CFM/ton
  • Auxiliary heat10 kW

Results

  • Design airflow1,200 CFM
  • Heating airflow1,260 CFM
  • Aux heat rise26.3 °F
  • Supply temp with aux at 70°F return96 °F
  • Aux capacity34,120 BTU/h

Frequently asked questions

Why does heat pump air feel cool?

Supply air is typically 95-105°F, below body temperature, so it feels cool even while heating effectively.

More airflow in heating?

Slightly higher airflow improves capacity and keeps head pressure sensible.

About this calculator