HVAC & Airflow

Hot Aisle Containment Calculator

Return airflow needed for a contained hot aisle.

Enter your values

ⓘ Live results

Results
Required return airflow
8,400 CFM
Containment volume
768 cu ft
Turnover rate
656.3 volumes/hr
Recommended return grille area at 500 FPM
16.8 sq ft

Quick answer

Contained hot aisle return airflow should match total rack supply airflow, with volume sized to avoid excess dead space.

Return CFM = supply CFM x 1.0-1.1

How to use the Hot Aisle Containment Calculator

  1. 1Sum the supply airflow of all racks feeding the hot aisle.
  2. 2Measure the containment aisle length, width and height.
  3. 3Size return grilles or ducted returns 5-10% above supply to keep the aisle slightly negative.

Worked example

Using the values the calculator loads with:

Inputs

  • Total rack supply airflow8000 CFM
  • Aisle length24 ft
  • Aisle width4 ft
  • Containment height8 ft

Results

  • Required return airflow8,400 CFM
  • Containment volume768 cu ft
  • Turnover rate656.3 volumes/hr
  • Recommended return grille area at 500 FPM16.8 sq ft

Frequently asked questions

Why oversize return slightly?

It prevents hot air from leaking around end doors back into the cold aisle.

Cold aisle containment instead?

Use the same supply-matches-demand principle but seal the cold aisle instead.

About this calculator

Results are estimates for general information. For medical, legal, structural or financial decisions, confirm with a qualified professional.