Rack Cooling Airflow Calculator

Per-rack CFM for a server cabinet.

Enter your values

ⓘ Live results

Results
Rack airflow needed
790 CFM
Heat output
17,060 BTU/hr
Tiles at 400 CFM each
2
Watts per CFM
6.33

Quick answer

A typical server rack needs roughly 160 CFM per kW at a 20F rise, so a 5kW rack needs about 800 CFM.

CFM = (W x 3.412) / (1.08 x dT)

How to use the Rack Cooling Airflow Calculator

  1. 1Enter the rack's total power draw in watts.
  2. 2Choose the allowable delta-T across the rack, commonly 20F.
  3. 3Match perforated tile or in-row airflow to the result.

Worked example

Using the values the calculator loads with:

Inputs

  • Rack power draw5000 W
  • Delta T20 F

Results

  • Rack airflow needed790 CFM
  • Heat output17,060 BTU/hr
  • Tiles at 400 CFM each2
  • Watts per CFM6.33

Frequently asked questions

What if racks vary a lot?

Calculate each rack separately, then balance tiles or dampers to match hot spots.

High density racks?

Above 10kW/rack, in-row or rear-door cooling usually beats raised-floor tiles.