HVAC & Airflow

Isolation Room Air Changes Calculator

ACH, exhaust and purge time for isolation rooms.

Enter your values

ⓘ Live results

Results
Exhaust airflow
324 CFM
Supply airflow
249 CFM (75 CFM offset)
Purge time
34.5 minutes
Room volume
1,620 cu ft
Pressure target
-2.5 Pa (-0.01 in wc) minimum

Quick answer

Airborne infection isolation rooms need at least 12 air changes per hour and negative pressure to the corridor.

purge time = 60 x ln(1/(1-removal)) / ACH

How to use the Isolation Room Air Changes Calculator

  1. 1Enter room dimensions and the required air changes — 12 ACH for new AII rooms.
  2. 2Set exhaust above supply by at least 50-75 CFM to hold negative pressure.
  3. 3Wait the purge time before the room is re-entered without protection.

Worked example

Using the values the calculator loads with:

Inputs

  • Room area180 sq ft
  • Ceiling height9 ft
  • Air changes12 ACH
  • Removal efficiency99.9 %

Results

  • Exhaust airflow324 CFM
  • Supply airflow249 CFM (75 CFM offset)
  • Purge time34.5 minutes
  • Room volume1,620 cu ft
  • Pressure target-2.5 Pa (-0.01 in wc) minimum

Frequently asked questions

Why 99.9% removal?

It is the standard benchmark for clearing airborne contaminants between patients.

Protective environment rooms?

Those are positive pressure with HEPA supply — the opposite of an isolation room.

About this calculator

Results are estimates for general information. For medical, legal, structural or financial decisions, confirm with a qualified professional.