HVAC & Airflow

Jumper Duct Size Calculator

Size a jumper duct to relieve a closed room.

Enter your values

ⓘ Live results

Results
Round jumper duct diameter
7 in
Minimum practical size
6 in round or 10x6 in rectangular boot
Two grille terminations needed
One in room ceiling, one near central return

Quick answer

Jumper ducts are typically sized for 400-500 FPM, similar to a branch return, based on the room's supply CFM.

Diameter = sqrt(4 x CFM / (velocity x pi)) x 12

How to use the Jumper Duct Size Calculator

  1. 1Enter the CFM supplied to the closed-door room.
  2. 2Use about 450 FPM design velocity for a quiet jumper duct.
  3. 3Terminate the duct with a grille in the room and another opening into the hallway or return plenum.

Worked example

Using the values the calculator loads with:

Inputs

  • Room supply CFM120 CFM
  • Design velocity450 FPM

Results

  • Round jumper duct diameter7 in
  • Minimum practical size6 in round or 10x6 in rectangular boot
  • Two grille terminations neededOne in room ceiling, one near central return

Frequently asked questions

Why not just undercut the door?

Undercuts alone rarely relieve enough airflow for a fully closed, actively supplied room; a jumper duct moves much more air quietly.

Does a jumper duct need a fan?

No, it relies on the pressure difference created by the supply air pressurizing the room.

About this calculator

Results are estimates for general information. For medical, legal, structural or financial decisions, confirm with a qualified professional.