HVAC & Airflow

Pool Dehumidification CFM Calculator

Evaporation load and airflow for an indoor pool.

Enter your values

ⓘ Live results

Results
Evaporation rate
80 lb/hour
Latent load
84,000 BTU/h
Ventilation at 6 ACH
4,000 CFM
Outdoor air minimum
400 CFM
Room pressure
Hold slightly negative to contain chloramines

Quick answer

Indoor pool rooms are sized on water surface evaporation, typically requiring 4-8 air changes per hour.

evaporation ≈ 0.1 x area x activity factor

How to use the Pool Dehumidification CFM Calculator

  1. 1Measure the water surface area and the room volume.
  2. 2Choose the activity level — splashing raises evaporation sharply.
  3. 3Hold the room 2°F above water temperature and slightly negative to neighbouring spaces.

Worked example

Using the values the calculator loads with:

Inputs

  • Water surface area800 sq ft
  • Room volume40000 cu ft
  • ActivityPublic pool (1.0)

Results

  • Evaporation rate80 lb/hour
  • Latent load84,000 BTU/h
  • Ventilation at 6 ACH4,000 CFM
  • Outdoor air minimum400 CFM
  • Room pressureHold slightly negative to contain chloramines

Frequently asked questions

Why keep air warmer than water?

It slows evaporation dramatically and cuts both latent load and condensation risk.

Dehumidifier or ventilation?

A dedicated pool dehumidifier with heat recovery costs far less to run than dumping heated air outside.