HVAC & Airflow

Restaurant Dining Ventilation Calculator

Outdoor air CFM for a restaurant dining room.

Enter your values

ⓘ Live results

Results
Outdoor air required
960 CFM
Per person rate
12 CFM
Total supply at 1.2 CFM/sq ft
2,400 CFM

Quick answer

Restaurant dining rooms typically need about 7.5 CFM per person plus 0.18 CFM per square foot of outdoor air.

CFM = 7.5 x people + 0.18 x area

How to use the Restaurant Dining Ventilation Calculator

  1. 1Count peak seated occupancy for the dining room.
  2. 2Enter the dining floor area, excluding the kitchen.
  3. 3Combine with makeup air sized separately for the kitchen hood system.

Worked example

Using the values the calculator loads with:

Inputs

  • Seated occupants80
  • Dining area2000 sq ft

Results

  • Outdoor air required960 CFM
  • Per person rate12 CFM
  • Total supply at 1.2 CFM/sq ft2,400 CFM

Frequently asked questions

Does this include the kitchen?

No — kitchens are sized separately by hood exhaust and matched makeup air.

Bar area?

Bars often need a slightly higher per-person rate due to denser seating and smoke/odour control.

About this calculator