HVAC & Airflow

Bar Ventilation Calculator

Outdoor air CFM for a bar or lounge.

Enter your values

ⓘ Live results

Results
Outdoor air required
630 CFM
Occupant density
16.7 sq ft/person
Total supply at 1.5 CFM/sq ft
1,500 CFM

Quick answer

Bars and lounges typically need about 7.5 CFM per person plus 0.18 CFM per square foot, often at higher density than dining rooms.

CFM = 7.5 x people + 0.18 x area

How to use the Bar Ventilation Calculator

  1. 1Estimate the peak standing-room occupancy for the bar area.
  2. 2Enter the bar floor area.
  3. 3Size supply air generously since bars run denser and warmer than dining rooms.

Worked example

Using the values the calculator loads with:

Inputs

  • Peak occupants60
  • Bar floor area1000 sq ft

Results

  • Outdoor air required630 CFM
  • Occupant density16.7 sq ft/person
  • Total supply at 1.5 CFM/sq ft1,500 CFM

Frequently asked questions

Why higher supply rate than dining?

Standing crowds generate more heat and CO2 per square foot than seated diners.

Smoking areas?

Any indoor smoking area needs dedicated high-CFM exhaust per local code, calculated separately.