HVAC & Airflow

Ridge Vent Length Calculator

Ridge vent run to balance attic intake.

Enter your values

ⓘ Live results

Results
Total NFA required
768 sq in
Ridge (exhaust) share
384 sq in
Ridge vent length
21.3 ft
Soffit intake share
384 sq in
Balance rule
50% high, 50% low

Quick answer

Ridge vent length is the required exhaust net free area divided by the vent's NFA per linear foot.

feet = required NFA (sq in) / NFA per foot

How to use the Ridge Vent Length Calculator

  1. 1Measure the attic floor area under the roof.
  2. 2Use 1:300 when a ceiling vapour retarder is present, otherwise 1:150.
  3. 3Split the ventilation half at the ridge and half at the soffits.

Worked example

Using the values the calculator loads with:

Inputs

  • Attic floor area1600 sq ft
  • Vent ratio1:300 (with vapour barrier)
  • Vent NFA per foot18 sq in/ft

Results

  • Total NFA required768 sq in
  • Ridge (exhaust) share384 sq in
  • Ridge vent length21.3 ft
  • Soffit intake share384 sq in
  • Balance rule50% high, 50% low

Frequently asked questions

What if the ridge is short?

Add roof or gable vents to make up the exhaust area, but never mix ridge and powered vents on the same attic.

Too much exhaust?

Yes — exhaust exceeding intake pulls conditioned air up through the ceiling.