HVAC & Airflow

Tons to CFM Calculator

Airflow needed for a cooling tonnage.

Enter your values

ⓘ Live results

Results
Required airflow
1,200 CFM
Cooling capacity
36,000 BTU/h
Return duct area needed
247 sq in at 700 FPM
In m³/h
2,039

Quick answer

Multiply tons by your design CFM per ton — 400 is the standard default.

CFM = tons x CFM per ton

How to use the Tons to CFM Calculator

  1. 1Enter the nominal tonnage of the system.
  2. 2Keep 400 CFM/ton unless your climate calls for 350 or 450.
  3. 3Size the return and supply duct for that airflow.

Worked example

Using the values the calculator loads with:

Inputs

  • Cooling capacity3 tons
  • Design airflow400 CFM/ton

Results

  • Required airflow1,200 CFM
  • Cooling capacity36,000 BTU/h
  • Return duct area needed247 sq in at 700 FPM
  • In m³/h2,039

Frequently asked questions

How much CFM for a 3 ton unit?

About 1,200 CFM at the standard 400 CFM per ton.

What if my ducts cannot carry it?

Undersized duct raises static pressure and cuts capacity; enlarge the return first, it is usually the bottleneck.