Server Room Cooling Calculator
Cooling tonnage and airflow for IT load.
Reviewed by James Whitfield · How we check our maths
Your values
ⓘ Live results
Results
- Cooling required
- 20,131 BTU/h
- In tons
- 1.68
- Total heat load
- 5,900 W
- Airflow at 20 °F ΔT
- 932 CFM
- Recommended unit
- 1.75 ton with N+1 redundancy
Quick answer
Server room cooling is dominated by IT load, where every watt drawn becomes a watt of heat.
The formula
BTU/h = (IT watts + other watts) x 3.412
Worked example
Worked example
Using the values the calculator loads with.
Inputs
- IT equipment load5000 W
- UPS and PDU losses10 %
- People in room1
- Lighting and other300 W
Result
- Cooling required20,131 BTU/h
- In tons1.68
- Total heat load5,900 W
- Airflow at 20 °F ΔT932 CFM
- Recommended unit1.75 ton with N+1 redundancy
How to use the Server Room Cooling Calculator
- 1Enter the measured or nameplate IT load in watts.
- 2Add UPS losses, occupants and lighting.
- 3Choose a unit with capacity headroom and plan redundancy.
Frequently asked questions
Should I use nameplate wattage?
Nameplate is conservative; measured load at the PDU is usually 40–60% of it.
Do I need humidity control?
Yes for larger rooms — very dry air raises static discharge risk and very humid air risks condensation.
About this calculator
- Built and reviewed by James Whitfield · How we build and test calculators
- Report an error