Bypass Damper Size Calculator

Bypass duct size for a zoned HVAC system.

Enter your values

ⓘ Live results

Results
Bypass airflow
1,200 CFM
Bypass duct diameter
19.1 in
Note
Excess bypass air raises supply temperature; use with caution or prefer variable-speed blower

Quick answer

A bypass duct is sized to handle the difference between full system CFM and the smallest zone's CFM, at a moderate design velocity.

Bypass CFM = total CFM - smallest active zone CFM

How to use the Bypass Damper Size Calculator

  1. 1Enter the system's total blower CFM and the smallest single zone's CFM.
  2. 2The bypass must handle the difference when only that small zone is open.
  3. 3Consider a variable-speed blower with zone control instead of a bypass to avoid coil freeze-up risk.

Worked example

Using the values the calculator loads with:

Inputs

  • Total system CFM1600 CFM
  • Smallest zone CFM400 CFM
  • Bypass velocity600 FPM

Results

  • Bypass airflow1,200 CFM
  • Bypass duct diameter19.1 in
  • NoteExcess bypass air raises supply temperature; use with caution or prefer variable-speed blower

Frequently asked questions

Is a bypass duct always needed?

Not with modern variable-speed equipment that can reduce airflow to match a small zone without a bypass.

What's the risk of an oversized bypass?

Excess air recirculating back to the return can overcool or overheat the return air and reduce dehumidification.