HVAC & Airflow

Elevator Shaft Ventilation Calculator

Vent area for an elevator hoistway per code.

Enter your values

ⓘ Live results

Results
Shaft cross-section area
56 sq ft
Required vent area
1.96 sq ft
In sq inches
282

Quick answer

Elevator hoistways are commonly required to have permanent venting equal to at least 3.5% of the shaft's cross-sectional area.

Vent area = shaft area x 3.5%

How to use the Elevator Shaft Ventilation Calculator

  1. 1Measure the elevator hoistway's cross-sectional floor area.
  2. 2Apply the local code percentage, commonly around 3.5% of that area.
  3. 3Locate the venting at or near the top of the hoistway per code.

Worked example

Using the values the calculator loads with:

Inputs

  • Shaft length8 ft
  • Shaft width7 ft
  • Required vent percentage3.5 %

Results

  • Shaft cross-section area56 sq ft
  • Required vent area1.96 sq ft
  • In sq inches282

Frequently asked questions

Is this for smoke control too?

Basic hoistway venting addresses heat/smoke from a fire in the shaft; dedicated smoke control systems may have separate requirements.

Does every jurisdiction use 3.5%?

Requirements vary by code edition and local amendments — confirm the exact figure with your local building authority.