Makeup Air Heating Load Calculator

Heating capacity needed to temper makeup air.

Enter your values

ⓘ Live results

Results
Heating capacity required
162,000 BTU/hr
In tons of heating equivalent
13.5 tons
Temperature rise
60 °F
Gas furnace input (80% AFUE)
202,500 BTU/hr input

Quick answer

Tempering makeup air uses about 1.08 BTU/hr per CFM per degree F of temperature rise, which quickly adds up to a large heating load for kitchen-size airflows.

BTU/hr = 1.08 x CFM x (indoor temp - outdoor design temp)

How to use the Makeup Air Heating Load Calculator

  1. 1Enter the makeup air CFM that must be tempered.
  2. 2Enter your indoor design temperature and winter outdoor design temperature.
  3. 3Read off the required heating capacity, converting to furnace input if needed.

Worked example

Using the values the calculator loads with:

Inputs

  • Makeup air CFM2500 CFM
  • Indoor design temp70 °F
  • Outdoor design temp10 °F

Results

  • Heating capacity required162,000 BTU/hr
  • In tons of heating equivalent13.5 tons
  • Temperature rise60 °F
  • Gas furnace input (80% AFUE)202,500 BTU/hr input

Frequently asked questions

Why is makeup air heating so large?

Every CFM of cold outside air needs continuous heating whenever the exhaust runs, and kitchen exhaust systems often move thousands of CFM.

Can heat recovery help?

Yes — an energy recovery ventilator or heat wheel can recover 50-80% of this load from the exhaust air stream.